QI-50-I Current Transformer

Share:


QI-50-I Current Transformer

QI-50-I

Current Transformer AC/DC  TRMS  LOOP POWERED


The QI-50-I is a AC/DC current transformer, galvanically isolated from the measuring circuit. The device is in the function and appearance very similar to a standard active TA, however, able to measure the DC component and AC TRMS. The transformer is powered 4-20mA current loop and therefore does not require a direct power supply. It ‘s the first Hall’s effect current transformer loop-powered with 0.5% accuracy on the market.

The QI-50-I has two dip-switches through which you can set the scale to 25 or 50A and select the monopolar or bipolar (see charts), the yellow led near the terminal will indicate the presence of the power supply. If you are using bipolar function on AC current, the value read will be 0 A (12 mA) because you are reading the average value.

Any changes made by dip-switch required to switch off the power supply. It’s a safety condition in order to prevent any manumission on the device.


MOUNTING:

The current transformer QI can be mounted in any position (see photo below), horizontal or vertical mounting, horizontal or vertical through the two hooks for DIN rail included in the box.



POWER SUPPLY Passive loop powered, 11...30V, Protections against polarity reversal and overtemperature.
ABSORPTION Less then 3,5mA
PROTECTION INDEX IP20
ACCURACY 0,5% F.S
RESOLUTION 12 bit
TEMPERATURE COEFFICIENT < 200 ppm/°C
WORKING TEMPERATURE -15...+65°C
STORAGE TEMPERATURE -40°C... +85°C
RESPONSE TIME 1000 ms
TYPE OF MEASURE TRMS (monopolar)
RANGE 50 Arms o 25 Arms dip-switch setting, bipolar (+/- 50A DC o +/-25A DC)
OUTPUT 4...20 mA
BAND WIDTH AT -3dB DC or 20...2000 Hz
ISOLATION 3 kV on bare wire
OVERLOAD 2000 A pulse, 300A continuos
CREST FACTOR 2
HYSTERESIS 0,15% f.s.
HUMIDITY 10...90% not condensing
ALTITUDE Up to 2000 m s.l.m
WEIGHT 72 g.
FILLING Epoxy Resins
BOX MATERIAL PBT, gray
MOUNTING Screw predisposition for vertical/ horizontal mounting, DIN Rail clips (included) for vertical/horizontal mounting
TERMINAL Removable terminals 5,08mm
DIP-SWITCH 2 poles
LED N°1 yellow ( Power on )
STANDARDS CE EN55022: 2010-12; EN55024: 2010-11;
DIMENSIONS 46,1x 63x 26,4 mm (terminal excluded)


CAUTION: Magnetic fields of high intensity can vary the values measured by the transformer. Avoid installation near permanent magnets, electromagnets or iron masses that induce strong changes in the magnetic field. If any irregularity recommend reorient or move the transformer in the area most appropriate.
High accuracy, yet very cost effective split-core AC/DC current transformers supplier in Malaysia & Singapore. Available in Penang, KL, Selangor, Johor & anywhere in Malaysia & Singapore.

Available in Penang, KL, Selangor, Johor & anywhere in Malaysia & Singapore.


Ketepatan tinggi, pembekal pengubah arus AC/DC teras pembahagi yang sangat berkesan dari segi kos di Malaysia & Singapura. Available in Penang, KL, Selangor, Johor & anywhere in Malaysia & Singapore.

Available in Penang, KL, Selangor, Johor & anywhere in Malaysia & Singapore.

Saturn Pyro menyediakan perkhidmatan kejuruteraan yang boleh dipercayai seperti Tinjauan Keselamatan Elektrik, Kajian Sistem Kuasa (Litar Pintas, Diskriminasi Aliran Beban & Perlindungan pada ETAP), Penilaian & Pelabelan Denyar Arka, Reka Bentuk Pembumian & Perlindungan Kilat, Pengukuran potensi Sentuhan & Langkah, Pengurusan Kualiti Kuasa , Audit Tenaga dan Penilaian Prestasi Pusat Data. Kami juga menyediakan Tinjauan Keselamatan Elektrik seperti Pemeriksaan pemasangan elektrik, Pengenalpastian risiko (bahaya elektrik), Semakan dokumentasi, prosedur operasi & penyelenggaraan, perancangan kontingensi, Penjanaan laporan dalam butiran potensi risiko dan rancangan untuk mitigasi, Pos laporan penutup perlaksanaan. Available in Pulau Pinang, Johor, Kuala Lumpur (KL), Selangor and anywhere in Malaysia / Singapore / Bangalore / India / Mumbai.



 Inquiry - QI-50-I Current Transformer